RESUMO
This work presents an innovative application of Frequency Response Analysis (FRA) in order to detect early degradation of Metal Oxide Surge Arresters (MOSAs). This technique has been widely used in power transformers, but has never been applied to MOSAs. It consists in comparisons of spectra, measured at different instants of the lifetime of the arrester. Differences between these spectra are an indicator that some electrical properties of the arrester have changed. An incremental deterioration test has been performed on arrester samples (with controlled circulation of leakage current, which increases the energy dissipation over the device), and the FRA spectra correctly identified the progression of damage. Although preliminary, the FRA results seemed promising, and it is expected that this technology could be used as another diagnostic tool for arresters.
RESUMO
Abstract The continuity of an electrical system's services is linked to its equipment's correct operation. The more correctly they worked, the higher the quality of the services provided. Thus, they must have their functioning scanned closely and that minor defects have their evolution monitored. This fact creates the possibility of making predictions about how long equipment can operate without compromising the system's continuity. This follow-up is proper for predictive maintenance. This paper presents three on-going COPEL Generation and Transmission projects in essential elements of its electrical system: circuit breakers, lightning arresters, and SF6 substation. The central idea of all monitoring projects is to check the early problem in this equipment and facilities.